Overview
The Allen‑Bradley PowerFlex 753 20F11ND011JA0NNNNN air-cooled three-phase AC frequency converter, chassis No. 2, three-phase, 480VAC, high-voltage voltage level ND7.5HP, HD5HP. The main body is IP00, with a cabinet partition added, it can reach IP20, in accordance with NEMA Open standard. Bottom axial flow fan for heat dissipation. Vertical wall-mounted control cabinet installation (height × width × depth): 432mm × 152mm × 203mm, approximately 8.16kg.
Specification
| Item | Specification |
|---|---|
| Product Series | PowerFlex 753 Air-Cooled General Purpose AC Drive |
| Input Voltage | 3-Phase 380–480V AC, 50/60Hz |
| Frame Size | Frame 2 |
| Enclosure Type | NEMA Open, IP00 / IP20 Protection |
| Pre-Charge Circuit & DC Bus Terminals | Built-in, Equipped |
| Rated Output Current | 11A |
| Normal Duty (ND) Power Rating | 7.5HP (5.5kW), 150% Overload 60s, 180% Overload 3s |
| Heavy Duty (HD) Power Rating | 5HP (3.7kW), 150% Overload 60s |
| Output Frequency Range | 0–599Hz |
| Supported Motors | 3-Phase Induction Motor, Permanent Magnet Synchronous Motor |
| EMC Filter | Pre-installed Line Common Mode Filter, CM Jumper Factory Fitted |
| Dynamic Brake Transistor | Built-in (External Brake Resistor Required) |
| Local HIM Panel | Not Included (Separate Purchase Required) |
| Embedded IO | Standard Built-in Digital & Analog IO |
| Communication | No Onboard Ethernet, Optional Comm Cards Supported |
| Cooling Method | Forced Air Cooling with Bottom Axial Fan |
| Overall Dimensions (H×W×D) | 432mm × 152mm × 203mm |
| Approximate Weight | 8.16 kg |
| Operating Ambient Temp | 0℃ ~ 50℃; Derating Required 50℃–60℃ |
| Storage & Transport Temp | -40℃ ~ 70℃ |
| Altitude Rating | Full Power ≤1000m, Derating Above 1000m |
| Certifications | UL, CSA, CE, UKCA, ATEX |
| Control Modes | V/F Scalar, Sensorless Vector, Closed-Loop Vector with Encoder |
| Built-in Functions | DeviceLogix Embedded Logic, PID, Safe Torque Off (STO), Predictive Diagnostics |
| Protection Functions | Overcurrent, Overvoltage, Undervoltage, Motor Overload, Module Overheat, Ground Fault, Phase Loss, Stall Protection |
| Typical Applications | Light Conveyors, Small Fans & Pumps, Packaging Machinery, Light Processing Equipment |
FAQ
1.What is the range of three-phase input voltage that the 20F11ND011JA0NNNNN inverter is compatible with?
The 480V high-voltage model, compatible with three-phase 380–480V AC, 50/60Hz industrial grid input
2.What are the overall dimensions and weight of Model 20F11ND011JA0NNNN?
Supported. The
- Overall machine dimensions (height × width × depth) 432mm × 152mm × 203mm
- Approximately 8.16 kilograms
3.What is the cabinet protection level and its corresponding NEMA standard for 20F11ND011JA0NNNNN?
The
- Protection level: The standard for the main body is IP00. After installing the front cover partition of the cabinet, it can reach IP20;
- NEMA standard: NEMA/UL Type Open (open cabinet).
4.What kind of heat dissipation and cooling structure is adopted by the 20F11ND011JA0NNNNN inverter?
The The bottom axial flow fan provides forced air cooling for heat dissipation.
Looking for Original New 20F11ND011JA0NNNNN PowerFlex 753 Three Phase AC Frequency Converter 480V
We supply this 20F11ND011JA0NNNNN mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now !