The Delta CP2000 Series Drive 37kW 480VAC 70A, 6-pulse diode rectification, built-in chopper, built-in PLC, multi-pump linkage, LCD display panel, emergency mode, Modbus RTU, BACnet, IEC61131-3 ladder diagram, PID regulator, IP20, for use only in control cabinets, C framework, PCB three-proof coating, net weight: 9.78kg
Specification
| Item | Specification |
|---|---|
| Model | VFD370CP43B-21 |
| Series | Delta CP2000 Fan&Pump Inverter |
| Rated Motor Power | 37kW (50HP) |
| Input | 3-phase 380~480VAC, 50/60Hz |
| ND Rated Current | 60A (Heavy Duty) |
| LD Rated Current | 73A (Light Duty) |
| ND Overload | 120%/60s, 160%/3s |
| LD Overload | 120%/60s |
| Max Output Frequency | 600Hz(V/F), 400Hz(SVC) |
| Control Mode | Multi V/F curve, Sensorless Vector(SVC) |
| Built-in DC Reactor | No |
| Built-in EMC Filter | No |
| Built-in Brake Chopper | Yes |
| Cooling | Forced air cooling, replaceable fan with life warning |
| PCB Protection | Full conformal coating |
| Built-in PLC | 10000 steps |
| Pump Group Control | Max 8 pumps linkage control |
| Native Communication | Modbus RTU, BACnet |
| Optional Bus Cards | Profibus-DP, CANopen, Modbus TCP, EtherNet/IP |
| Dimension(W×H×D) | 210mm × 400mm × 251mm |
| Net Weight | 9.78kg |
| Protection Grade | IP20 |
| Full-load Ambient Temp | ND:-10~50℃; LD:-10~40℃ |
| Non-derating Altitude | ≤1000m |
| Certifications | CE, UL, cUL |
FAQ
1.Does the VFD370CP43B-21 model have built-in DC reactor, EMC filter and braking chopper?
The
- Built-in braking chopper
- Without filter
- Without DC reactor
2.What are the requirements for the reserved ventilation space for the upper and lower air ducts on the VFD370CP43B-21?
Supported. The
- Vertical up-down air ducts: The air outlet above the frequency converter is reserved with a size of ≥80mm, and the air inlet below is reserved with a size of ≥60mm;
- Left and right lateral: Both sides are reserved with a size of ≥30mm;
- Hard requirements: Zero stacking and close contact stacking of the frequency converter are prohibited; for multiple units arranged longitudinally, a heat insulation and flow guiding partition must be added to prevent hot air from directly blowing onto the frequency converter above.
3.What are the overall length, width, height and net weight of the VFD370CP43B-21 product?
The
- Overall dimensions of the machine (width 210mm × height 400mm × depth 251mm)
- Net weight of the machine: 9.78kg
- Matching frame: C frame, protection level IP20.
4.What kind of operation panel is standardly equipped in the VFD370CP43B-21 model? Does the panel support remote extension of wiring installation?
The
- KPC-CC01 LCD liquid crystal display operation panel, with backlit LCD screen, supporting hot-swappable panel disassembly and assembly,
- supporting remote external extension of the panel, regular reliable distance: ordinary network cable can be stably extended up to 10-20 meters, the longest compliant extension cable provided by the manufacturer is 16 feet (approximately 4.8 meters)
Looking for Original New Delta Delta VFD370CP43B-21 CP2000 Series Drive 37kW 480VAC 70A
We supply this VFD370CP43B-21 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews
There are no reviews yet.