Overview
The Delta CP2000 Series AC Drive, 460V three-phase, G2 frame, built-in Class A EMC filter, braking chopper, 6-pulse rectification, built-in PLC, supports sequential logic, 8-channel DI, 3-channel DO, 2-channel AI, 2-channel AO, forced air cooling, PCB with 3C2 anti-corrosion coating, wall-mounted installation, weight 114 kg
Specification
| Item | Spec |
|---|---|
| Model | VFD2200CP43A‑21 |
| Series | CP2000 |
| Rated motor | 220 kW,460V 3‑phase |
| HD rated current | 440 A |
| ND rated current | 490 A |
| Frame | G2 |
| IP class | IP20 |
| Built‑in DC reactor | No |
| Built‑in EMC filter | Yes (Class A) |
| Built‑in brake chopper | Yes |
| Built‑in PLC | 10000 steps |
| Weight | 114 kg |
FAQ
1.What are the overall width, height and depth dimensions as well as the net weight of the VFD2200CP43A-21 frame model?
The
- Frame model: G2 frame
- Overall dimensions of the machine (width 500 mm × height 1240 mm × depth 397 mm)
- Net weight of the machine: 114 kg.
2.What is the minimum reserved ventilation spacing for the front and rear, as well as the left and right air ducts of VFD2200CP43A-21?
Supported. The
- Minimum clearance above (exhaust outlet): ≥ 200 mm
- Minimum clearance below (intake inlet): ≥ 200 mm
- Minimum clearance on both sides (left and right): ≥ 100 mm
3.Does the VFD2200CP43A-21 cooling fan support disassembly and replacement independently? Is it allowed to perform maintenance by hot-plugging while the device is powered on?
The
- Cooling fan: Allows for separate disassembly and replacement. Plug-in modular fan assembly.
- Do not perform maintenance while the device is powered on. The entire machine must be powered off for operation.
4.The VFD2200CP43A-21 board has built-in digital DI and DO channels, as well as analog AI and AO channels. How many channels are there for each type?
The
- Digital DI (MI Multi-Function Input): 8 channels, NPN/PNP switchable
- Digital DO: 3 relay non-polarized output contacts
- Analog AI: 2 channels (AVI voltage input, ACI current input)
- Analog AO: 2 channels (AFM, AOM, voltage/current mode can be switched by jumper)
Looking for Original New VFD2200CP43A-21 Delta CP2000 Series AC Drive 220kW 460A 300HP
We supply this VFD2200CP43A-21 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews