Overview
The Delta CP2000 Series AC Drive 460V three-phase, E1 frame, DC reactor, built-in PLC, 6-pulse rectification, full coverage of PCB circuit board with three-layer protection coating, prohibited from direct outdoor rain exposure, 8 water pumps linked operation, forced air cooling, fans can be disassembled and replaced separately, IP20 sealed cabinet version, wall-mounted screw installation, RJ45 interface
Specification
| Item | Specification |
|---|---|
| Model | VFD1100CP43A‑21 |
| Series | CP2000 Fan‑Pump Drive |
| Rated motor power | 110kW(150HP),3‑phase 380‑480V |
| Frame size | E1 |
| Output current ND/LD | 180A / 220A |
| Rectifier | 6‑pulse |
| Built‑in DC reactor | Yes |
| Built‑in EMC filter | No |
| Built‑in braking chopper | No |
| Built‑in PLC steps | 10000 steps(RTC real‑time clock) |
| Max pump quantity | 8 pumps |
| Dimension(W×H×D) | 410 mm × 775 mm × 305 mm |
| Weight | 66.0 kg |
| Cooling | Forced air cooling, replaceable fan |
| Enclosure rating | IP20 |
| Keypad | KPCC‑01, remote extension supported |
| PCB Conformal coating | Class3C2 |
| Operation temp | 0‑50℃ full rating |
FAQ
1.VFD1100CP43A-21 – Overall width, height and depth dimensions of the machine, net weight of the machine, frame model?
The
- Frame model: E1 frame
- Net weight of the entire machine: 66.0 kg
- Overall dimensions of the machine (width 410 mm × height 775 mm × depth 305 mm)
2.How many water pumps can the VFD1100CP43A-21 single inverter directly control at most?
Supported. The Scheduled cycle mode (all pumps operate in variable frequency mode in rotation, without a constant frequency bypass): The original system can have up to 8 pumps, and only 1 pump operates in variable frequency mode at any given time.
3.Does the VFD1100CP43A-21 cooling fan support disassembly and replacement independently?
The Supports separate disassembly and replacement. It has a fan lifespan warning function. Hot swapping is not supported. Replacement requires the entire machine to be powered off.
4.What model of operation panel is standardly equipped at the factory for VFD1100CP43A-21? Does it support remote extension? What is the maximum wiring distance in meters?
The KPCC-01 LCD operation panel, supports it. The interface is RJ45. It is necessary to use the original dedicated extension cable provided by Delta. The maximum stable wiring distance: 50 meters.
Looking for Original New VFD1100CP43A-21 Delta CP2000 Series AC Drive 110kW 150HP 220A
We supply this VFD1100CP43A-21 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now