Overview
The Mitsubishi MELSEC iQ-R series, 8-channel A/D analog input module, 18-point M3 screw terminal block, does not support HART communication, 80μs/CH single-channel conversion speed, 30mA input current, intelligent 16-point I/O, resolution 625nA, iQ-R backplane rack slot installation.
Specification
| Item | Specification |
|---|---|
| Model | R60ADI8 |
| Series | MELSEC iQ‑R PLC |
| Type | Analog input module(current‑only) |
| Channels | 8CH, DC 0‑20mA |
| Digital output | 0‑32000 |
| Conversion speed | 80 μs / channel |
| Accuracy(25℃) | ±0.1%FS |
| Accuracy(0‑55℃) | ±0.3%FS |
| I/O occupied points | 16 intelligent points |
| DC5V current consumption | 0.22 A |
| Dimension(W×H×D) | 27.8 mm × 106 mm ×131 mm |
| Weight | 0.21 kg |
| Terminal | 18‑point screw terminal block |
| Isolation | Photo‑coupler(terminal‑PLC power); No channel‑to‑channel isolation |
| Protection class | IP00 |
FAQ
1.What are the overall width, height and depth dimensions as well as the net weight of the R60ADI8 machine?
The
- Overall dimensions of the machine (width 27.8 mm × height 106 mm × depth 131 mm)
- Net weight of the machine: 0.12 kg
2.How many amperes does the R60ADI8 module consume on the DC5V backplane? Is an external 24V power supply required?
Supported. The
- DC5V backplane current consumption: 0.22 A
- No external 24V power supply is required. All the module power is derived from the PLC backplane’s DC5V.
3.How many intelligent I/O points does the R60ADI8 module occupy?
The Occupies 16 points of intelligent I/O.
4.Are the channels of the R60ADI8 module isolated from each other? What is the isolation method between the terminals and the PLC power supply?
The
- Channel – Channel: No isolation (non-isolated), all analog channels share the reference ground.
- The external signal side of the terminal and the internal backplane power supply of the PLC: optocoupler (opto-isolator) isolation
- Isolation withstand voltage: AC 500Vrms, 1 minute.
Looking for Original New R60ADI8 MELSEC iQ-R Series Analog Input module With 8 Channels
We supply this R60ADI8 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now