SMC soft starters are widely used in industrial motor control applications to reduce starting current, mechanical shock, and voltage drop during motor acceleration. However, like any electronic motor controller, an SMC soft starter can display fault conditions caused by power supply problems, motor issues, incorrect parameter settings, SCR failures, bypass problems, overheating, or communication faults.
This guide explains common SMC soft starter fault codes and troubleshooting procedures, with a focus on the SMC-3, SMC-Flex, and SMC-50 product families.
The most common troubleshooting topics include:
- Phase loss
- Stall and jam conditions
- Start timeout
- Open gate / SCR gate faults
- Shorted SCR
- Bypass faults
- SCR overtemperature
- Current imbalance
- Line voltage imbalance
- Motor overload
- No-load conditions
- Control voltage problems
Important: Fault numbering is not identical across SMC-3, SMC-Flex, and SMC-50. Always identify the exact SMC model and consult the corresponding Allen-Bradley manual before replacing a power module or control module.
1. SMC Soft Starter Fault Codes at a Glance
The Bulletin 150 SMC family includes several generations of solid-state motor controllers.
The three commonly encountered families are:
| Product Family | Typical Bulletin | Main Application |
|---|---|---|
| SMC-3 | Bulletin 150-C | Compact solid-state soft starter |
| SMC-Flex | Bulletin 150-F | Advanced soft starter with diagnostics and communication |
| SMC-50 | Bulletin 150-S | Advanced soft starter with extensive motor protection and diagnostics |
The SMC-Flex manual, for example, identifies separate codes for line loss, shorted SCR, open gate, SCR overtemperature, bypass faults, overload, jam, stall, and other conditions.
The SMC-50 uses a more extensive diagnostic system. Its LED codes can be supplemented by detailed fault information through a HIM or configuration software. For example, Current Imbalance is associated with fault code 42, while the SMC-50 also provides separate diagnostics for open bypass, SCR overtemperature, line loss, and open gate conditions.
2. Phase Loss / Line Loss Fault
Typical Symptoms
A phase-loss fault occurs when the SMC detects that one of the three input phases is missing or abnormal.
Typical symptoms include:
- Motor does not start
- Soft starter trips before acceleration
- One phase has significantly lower voltage
- Fuse or circuit breaker has opened
- Loose power connection
- Damaged contactor
- Incorrect motor wiring
In the SMC-Flex, the basic line-loss codes are:
| Fault Code | Fault |
|---|---|
| 1 | Line Loss A |
| 2 | Line Loss B |
| 3 | Line Loss C |
AB specifies missing supply phase and improper motor connection as possible causes and recommends checking line/load connections, fuses, open leads, and power quality.
Common Causes
The most common causes include:
- Blown input fuse
- Loose terminal connection
- Damaged contactor
- Broken motor cable
- Missing motor phase
- Incorrect wiring
- Severe voltage imbalance
- Poor electrical connection
- Damaged SMC power module
Troubleshooting Steps
Step 1: Measure incoming voltage
With appropriate electrical safety procedures, measure:
- L1-L2
- L2-L3
- L1-L3
The three measurements should be reasonably balanced.
Step 2: Check the input protection
Inspect:
- Fuses
- Circuit breakers
- Disconnect switches
- Main contactor
A single open fuse can cause a phase-loss fault.
Step 3: Check the load side
Inspect:
- T1
- T2
- T3
- Motor terminals
- Motor cable
- Terminal blocks
Step 4: Check motor winding resistance
With the equipment properly isolated, compare the motor winding resistance between phases.
A significant difference can indicate a motor winding problem.
Step 5: Check the SMC power module
If the supply and motor wiring are correct but the fault remains, the SMC power module or SCR assembly may require further testing.
3. Jam / Stall / Locked-Rotor Conditions
A motor that receives a start command but cannot accelerate can generate a Jam or Stall condition.
This is particularly important for:
- Pumps
- Compressors
- Conveyors
- Crushers
- Fans
- Mixers
- High-inertia machinery
Jam vs. Stall
These two conditions should not be confused.
For SMC-Flex, AB lists:
- Code 24 — Jam
- Code 25 — Stall
A Jam condition occurs when motor current exceeds the programmed jam level.
A Stall condition occurs when the motor has not reached full speed by the end of the programmed ramp time.
Therefore, an engineer may describe the field symptom as “motor blocked” or “start timeout,” but the actual SMC diagnostic code can be different depending on the model and configured protection.
Common Causes
Possible causes include:
- Mechanical blockage
- Pump impeller jam
- Conveyor obstruction
- Excessive load
- Motor bearing failure
- Brake not releasing
- Insufficient starting torque
- Ramp time set incorrectly
- Current limit set too low
- Motor FLC incorrectly configured
- Motor/load mismatch
Troubleshooting Steps
Step 1: Disconnect the mechanical load
Where safe and appropriate, determine whether the motor can rotate freely.
Step 2: Check the motor nameplate
Verify:
- Rated current
- Rated voltage
- Frequency
- Motor horsepower/kW
- Connection type
Step 3: Check the SMC motor FLC setting
The programmed motor full-load current should correspond to the motor nameplate and the installation configuration.
Step 4: Check the acceleration ramp
If the acceleration time is too short for a high-inertia load, the motor may not reach full speed.
Increase the ramp time where appropriate.
Step 5: Check current limit settings
An excessively low current limit may prevent the motor from producing sufficient starting torque.
Step 6: Inspect the mechanical system
Check for:
- Locked bearings
- Blocked pumps
- Jammed conveyors
- Closed valves
- Mechanical brakes
- Excessive friction
- Misaligned couplings
4. Start Timeout / Motor Does Not Reach Full Speed
A common field description is:
“The motor starts but never reaches full speed before the soft starter times out.”
This condition can be related to Stall, acceleration settings, current limiting, or an excessive mechanical load.
In the SMC-Flex, Stall is associated with fault code 25 when the motor has not reached full speed by the end of the programmed ramp time.
Possible Causes
- Acceleration ramp too short
- Starting torque too low
- Current limit too low
- Excessive load
- High motor inertia
- Mechanical brake not released
- Incorrect motor FLC
- Incorrect soft-start configuration
- Motor problem
Recommended Troubleshooting
- Record the motor current during starting.
- Compare the current with the motor nameplate.
- Check the programmed acceleration time.
- Verify the initial torque or current-limit setting.
- Check whether the load can rotate freely.
- Check for a mechanical brake.
- Verify motor wiring.
- Test the motor without the mechanical load if possible.
A useful diagnostic question is:
Does the motor accelerate slowly, or does it remain almost stationary?
If it accelerates slowly, parameter settings or excessive inertia may be involved.
If it does not accelerate at all, investigate mechanical blockage, insufficient torque, wiring, SCR firing, or motor problems.
5. Shorted SCR Fault
An SCR is the main semiconductor switching device used by a solid-state soft starter.
A shorted SCR means that one of the power poles may remain electrically conducting when it should not.
For SMC-Flex, the shorted SCR codes are:
| Code | Fault |
|---|---|
| 4 | Shorted SCR A |
| 5 | Shorted SCR B |
| 6 | Shorted SCR C |
Typical Symptoms
- Motor may receive voltage when it should be stopped
- Soft starter may fail its pre-start check
- Fault appears immediately after power-up or before starting
- Motor may not stop correctly
- Bypass operation may be abnormal
Troubleshooting
Step 1: Isolate power
Follow the site’s lockout/tagout procedure.
Step 2: Inspect the power module
Check for:
- Burn marks
- Physical damage
- Thermal damage
- Loose connections
Step 3: Perform appropriate SCR testing
An experienced technician can perform resistance or semiconductor tests according to the applicable AB service procedure.
Step 4: Check for external causes
Repeated SCR failure can be caused by:
- Short circuits
- Excessive current
- Incorrect protection
- Voltage transients
- Motor faults
- Incorrect application
Replacing the SCR without identifying the original cause may result in another failure.
6. Open Gate / SCR Gate Fault
An Open Gate fault indicates a problem with the SCR firing path.
For SMC-Flex:
| Code | Fault |
|---|---|
| 7 | Open Gate A |
| 8 | Open Gate B |
| 9 | Open Gate C |
AB lists open gate circuitry and loose gate leads as possible causes. Recommended checks include resistance testing, power-module inspection, and checking the gate connections between the power module and control module.
Common Causes
- Loose gate lead
- Damaged SCR
- Open gate circuit
- Damaged power module
- Poor connection between control and power module
- Control module failure
Troubleshooting Steps
- Record the exact phase indicated by the fault.
- Power down and isolate the equipment.
- Inspect the gate wiring.
- Check connectors between the control module and power module.
- Perform the applicable resistance test.
- Compare the suspect phase with the other phases.
- Replace the power module if testing confirms an internal failure.
7. Bypass Fault
Bypass operation allows the motor current to flow through a bypass path after the motor reaches the required operating condition.
A bypass fault can cause the soft starter to remain in a fault state even though the motor appears to have started.
For SMC-Flex, bypass faults are:
| Code | Fault |
|---|---|
| 13 | Open Bypass A |
| 14 | Open Bypass B |
| 15 | Open Bypass C |
AB documentation identifies low control voltage and a malfunctioning power-module bypass as possible causes. It also recommends checking the control-module connections and verifying that auxiliary configuration is not incorrectly set for an external bypass.
Common Causes
- Low control voltage
- Bypass mechanism failure
- Damaged power module
- Loose control-module connections
- Incorrect auxiliary configuration
- External bypass wiring problem
Troubleshooting
Step 1: Check control voltage
Verify the control supply at the appropriate terminals.
Step 2: Check the bypass path
Inspect the bypass circuit and associated connections.
Step 3: Check auxiliary configuration
Incorrect auxiliary settings can cause unexpected bypass behavior.
Step 4: Inspect the power module
If the control system is correct but the bypass does not operate correctly, the power module may require replacement.
8. SCR Overtemperature
Overtemperature is another common SMC fault.
For SMC-Flex:
- Code 10 = PTC Power Pole
- Code 11 = SCR Overtemp
The SMC-Flex manual identifies blocked ventilation, excessive controller duty cycle, fan failure, excessive ambient temperature, failed thermistor, and control/power-module problems among possible causes.
The SMC-50 similarly monitors SCR/power-pole temperature and provides specific diagnostics for SCR overtemperature and PTC power-pole conditions.
Common Causes
- Cabinet temperature too high
- Insufficient ventilation
- Fan failure
- Excessive starting frequency
- Excessive duty cycle
- Oversized load
- Loose electrical connections
- Failed temperature sensor
- Damaged power module
Troubleshooting Steps
- Measure cabinet ambient temperature.
- Check cabinet ventilation.
- Inspect cooling fans.
- Check for blocked air passages.
- Review motor starting frequency.
- Check the soft starter’s rated duty cycle.
- Check current during operation.
- Allow the controller to cool before restarting.
- Investigate the thermistor/power module if the fault returns immediately.
Do not simply reset the fault repeatedly.
Repeated overheating can indicate an application problem or a failing power module.
9. Current Imbalance
Current imbalance means the motor currents on the three phases are significantly different.
The condition can originate from either the motor/load side or the soft starter/power side.
The SMC-50 identifies Current Imbalance as fault code 42.
Possible Causes
Power supply problems
- Voltage imbalance
- Loose terminal
- Damaged fuse
- High-resistance connection
Motor problems
- Winding imbalance
- Insulation problems
- Motor damage
- Unequal phase resistance
Soft starter problems
- SCR degradation
- Power module problem
- Gate-firing problem
- Current sensor problem
Mechanical problems
- Uneven mechanical load
- Bearing problems
- Coupling problems
Troubleshooting Procedure
Measure all three motor currents under the same operating condition.
For example:
- L1 current
- L2 current
- L3 current
Then compare the readings.
If voltage is balanced but current is significantly unbalanced, investigate the motor and SMC power stage.
If both voltage and current are unbalanced, investigate the incoming power system first.
10. Line Voltage Imbalance
Voltage imbalance should be investigated before replacing the soft starter.
The SMC-Flex identifies Line Unbalance as code 19. Rockwell documentation indicates that this can occur when the supply imbalance exceeds the programmed threshold or when the delay time is too short for the application.
Check
- Incoming voltage
- Transformer output
- Circuit breaker
- Fuse condition
- Contactor
- Terminal tightness
- Cable condition
- Motor connection
A loose terminal can create a high-resistance connection that produces both voltage and current imbalance.
11. Overload Fault
An overload fault indicates that the motor has exceeded its programmed thermal/current protection characteristics.
For SMC-Flex, Overload is code 22.
Common Causes
- Motor mechanically overloaded
- Motor FLC incorrectly programmed
- Incorrect overload class
- Excessive starting time
- Excessive current
- Mechanical friction
- Pump or conveyor overload
- Motor damage
Troubleshooting
- Verify motor nameplate FLA.
- Verify the programmed motor FLC.
- Check motor current.
- Inspect the mechanical load.
- Check the acceleration ramp.
- Check overload class.
- Check motor temperature.
- Check motor insulation and windings if necessary.
12. No Load / Open Load Fault
A no-load condition can occur when the SMC detects that the motor circuit is not properly connected.
Possible causes include:
- Open motor cable
- Loose terminal
- Open motor winding
- Contactor problem
- Incorrect wiring
- Motor disconnected
SMC-Flex uses codes 16, 17, 18 and 40 for no-load conditions depending on the specific diagnostic source.
Check the entire circuit from the SMC output terminals to the motor.
13. Practical Troubleshooting Sequence
When an SMC soft starter reports a fault, do not immediately replace the soft starter.
Use this sequence:
Step 1 — Record the exact fault
Record:
- Fault number
- Phase indication
- LED pattern
- HIM message
- Date/time
- Operating condition
Step 2 — Identify the exact SMC model
Determine whether the controller is:
- SMC-3
- SMC-Flex
- SMC-50
Also record:
- Catalog number
- Series
- Firmware revision if available
Step 3 — Check incoming power
Measure:
- L1-L2
- L2-L3
- L1-L3
Step 4 — Check motor wiring
Inspect:
- T1
- T2
- T3
- Motor terminals
- Motor cable
- Grounding
Step 5 — Check motor condition
Check:
- Winding resistance
- Insulation resistance
- Mechanical rotation
- Bearings
- Coupling
- Brake
- Load
Step 6 — Check parameters
Verify:
- Motor FLC
- Start mode
- Start ramp
- Current limit
- Initial torque
- Overload class
- Jam level
- Stall settings
- Auxiliary configuration
Step 7 — Check the SMC power stage
If external conditions are normal, investigate:
- SCRs
- Power module
- Gate circuit
- Temperature sensors
- Current sensors
- Bypass circuit
Step 8 — Clear the fault and test
After correcting the root cause:
- Clear the fault.
- Start the motor.
- Monitor current.
- Monitor voltage.
- Observe acceleration.
- Check bypass operation.
- Confirm that the fault does not return.
14. SMC Model Numbers
The Bulletin 150 family contains a wide range of SMC soft starters.
The following are examples of commonly encountered catalog numbers from the SMC-3 and SMC-50 families. Catalog number suffixes can identify voltage rating, control voltage, enclosure/configuration, and other options, so the complete catalog number should always be verified before ordering a replacement.
SMC-3 Examples
- 150-C3NBD
- 150-C9NBD
- 150-C16NBD
- 150-C19NBD
- 150-C25NBD
- 150-C30NBD
- 150-C37NBD
- 150-C43NBD
- 150-C60NBD
- 150-C85NBD
The SMC-3 product range includes 3, 9, 16, 19, 25, 30, 37, 43, 60 and 85 A ratings, with different voltage/control-voltage configurations.
SMC-50 Examples
- 150-S108NBD
- 150-S108NBR
- 150-S135NBD
- 150-S135NBR
- 150-S201NBD
- 150-S201NBR
- 150-S251NBD
- 150-S251NBR
- 150-S317NBD
- 150-S361NBD
- 150-S480NBD
- 150-S108NUR
- 150-S135NUR
- 150-S201NUR
- 150-S251NUR
- 150-S108UPGD
- 150-S108UPGR
- 150-S135UPGD
- 150-S135UPGR
- 150-S201UPGUR
The SMC-50 nomenclature covers current ratings including 108 A, 135 A, 201 A, 251 A, 317 A, 361 A and 480 A, with voltage and control-voltage options determined by the catalog-number suffix.
15. SMC-3 vs. SMC-Flex vs. SMC-50
| Feature | SMC-3 | SMC-Flex | SMC-50 |
|---|---|---|---|
| Product family | Bulletin 150-C | Bulletin 150-F | Bulletin 150-S |
| Main purpose | Compact soft starting | Advanced motor control | Advanced diagnostics and motor protection |
| Fault diagnostics | Basic | Advanced | Extensive |
| HIM support | Limited/configuration dependent | Yes | Yes |
| Communication options | Application dependent | Yes | Yes |
| Bypass options | Model dependent | Available | Available |
| Advanced motor protection | Basic | Extensive | Extensive |
| Typical troubleshooting | Power, motor, SCR | Power, motor, SCR, bypass, communication | Power, motor, SCR, bypass, thermal, current/voltage diagnostics |
The SMC-50 provides a significantly more extensive diagnostic system than the simpler SMC-3, while SMC-Flex provides detailed fault codes covering line loss, SCR faults, gate faults, bypass faults, overload, jam, stall, communication and other conditions.
16. Frequently Asked Questions
What does an SMC soft starter phase loss fault mean?
It generally means that the controller has detected a missing or abnormal phase on the incoming supply or motor circuit. Check fuses, contactors, terminals, motor cables, and incoming voltage before replacing the soft starter.
What causes an SMC soft starter to trip during starting?
Common causes include excessive mechanical load, insufficient starting torque, incorrect motor FLC, current limit settings, shorted/open SCRs, phase loss, and an acceleration ramp that is inappropriate for the application.
What causes an SMC soft starter SCR fault?
SCR faults can result from an internally failed power module, electrical overstress, loose connections, gate-driver problems, voltage transients, or an external motor/system fault.
What causes an SMC bypass fault?
Typical causes include low control voltage, bypass circuit problems, power-module failure, loose connections, or incorrect auxiliary configuration.
Why does an SMC soft starter overheat?
Possible causes include excessive ambient temperature, insufficient cabinet ventilation, failed cooling fans, excessive starting frequency, excessive duty cycle, high motor current, or a failing power module.
Why is motor current unbalanced?
Current imbalance can originate from the incoming power supply, motor windings, motor cable, loose connections, mechanical loading, SCR/power-module problems, or current-sensing circuitry.
17. Final SMC Soft Starter Troubleshooting Checklist
Before replacing an Allen-Bradley SMC soft starter, check the following:
- Exact SMC model identified
- Complete catalog number recorded
- Series identified
- Fault code recorded
- Incoming three-phase voltage checked
- Fuses checked
- Main contactor checked
- Power terminals checked
- Motor cable checked
- Motor winding resistance checked
- Motor insulation checked
- Motor mechanical load checked
- Motor FLC verified
- Acceleration ramp checked
- Current limit checked
- Overload setting checked
- Jam/Stall settings checked
- SCR condition checked
- Gate connections checked
- Bypass circuit checked
- Cabinet ventilation checked
- Cooling fan checked
- Control voltage checked
- Current imbalance checked
- Voltage imbalance checked
- Fault history reviewed
- Fault cleared and motor retested
Conclusion
SMC soft starter faults should be diagnosed systematically rather than by simply replacing the controller.
A phase-loss fault may originate from a fuse or loose terminal. A stall or jam condition may be caused by the mechanical load rather than the SMC itself. An open-gate or shorted-SCR fault may indicate a failed power module, while an overtemperature fault can be related to cabinet ventilation, duty cycle, or excessive starting frequency.
The exact fault-code system also depends on the SMC family. For example, SMC-Flex uses dedicated codes for Line Loss, Shorted SCR, Open Gate, Open Bypass, Jam and Stall, while SMC-50 provides a broader diagnostic system with additional motor and power-quality monitoring.
For troubleshooting or replacement, always verify the complete catalog number, voltage rating, control voltage, current rating, series, and application configuration before selecting a replacement SMC soft starter.
For SMC-3, SMC-Flex and SMC-50 replacement parts, manuals, and industrial automation components, contact an experienced industrial automation supplier for catalog-number verification before ordering.