Overview
The Delta CP2000 Series AC Drive F1 frame, 6-pulse rectification, built-in DC reactor, built-in PLC, supports sequential logic control, built-in Modbus-RTU, BACnet, PCB circuit board triple protection coating, only circuit board protection, forced air cooling, with fan life warning, LCD operation panel, supports RJ45 interface for remote extension, wall-mounted screw installation.
Specification
| Item | Specification |
|---|---|
| Model | VFD1600CP43A‑21 |
| Series | CP2000 Fan‑Pump Drive |
| Rated motor power | 160kW(215HP),3‑phase 380‑480V |
| Frame size | F1 |
| Output current ND/LD | 295A / 310A |
| Rectifier | 6‑pulse |
| Built‑in DC reactor | Yes |
| Built‑in EMC filter | No |
| Built‑in braking chopper | No |
| Built‑in PLC steps | 10000 steps(RTC real‑time clock) |
| Max pump quantity | 8 pumps |
| Dimension(W×H×D) | 480 mm × 840 mm × 330 mm |
| Weight | 109.0 kg |
| Cooling | Forced air cooling, modular replaceable fan |
| Enclosure rating | IP20 |
| Keypad | KPCC‑01, support remote extension |
| PCB Conformal coating | Class3C2 |
| Full‑rating ambient temp | 0‑50℃ |
FAQ
1.VFD1600CP43A-21 – Overall width, height and depth dimensions of the machine, net weight of the machine, frame model?
The
- Overall dimensions of the machine (width 480 mm × height 840 mm × depth 330 mm)
- Net weight of the machine: 109.0 kg
- Frame model: F2 frame
2.What are the rated output currents in amperes for heavy load and light load of VFD1600CP43A-21?
Supported. The
- ND (Heavy Load, General Load) rated output current: 295A
- LD (Light Load, Variable Torque) rated output current: 310A
- Overload capacity in heavy load mode: 120% – 60 seconds; Overload capacity in light load mode: 110% – 60 seconds.
3.The reserved ventilation spacing for the front, rear, left and right air ducts of VFD1600CP43A-21?
The
- Above: ≥150 mm
- Below: ≥150 mm
- Each side (left and right): ≥50 mm
4.The maximum output frequency of the VFD1600CP43A-21V/F mode and the SVC mode, and what is the low-frequency starting torque of the SVC mode at 0.5Hz?
The
- The maximum output frequency in V/F mode: 599 Hz
- The maximum output frequency in the SVC non-sensing vector mode: 599 Hz
- The low-frequency starting torque of 0.5Hz in the SVC mode: 150% of the rated torque
Looking for Original New VFD1600CP43A-21 Delta CP2000 Series AC Drive 460V 160kW 310A 215HP
We supply this VFD1600CP43A-21 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews