The Delta CP2000 Series AC Drive, 460V ,three-phase, F1 frame, LD light load 310A, ND heavy load 295A, DC reactor, built-in PLC, supports sequential logic control, Modbus‑RTU, BACnet, PCB circuit board triple coating, forced air cooling, IP00 open bare machine, wall-mounted screw installation, prohibited zero stacking close side-by-side installation.
Specification
| Item | Specification |
|---|---|
| Model | VFD1600CP43A‑00 |
| Series | CP2000 Fan‑Pump Drive |
| Rated motor power | 160kW(215HP),3‑phase 380‑480V |
| Frame size | F1 |
| Output current ND/LD | 295A / 310A |
| Rectifier | 6‑pulse |
| Built‑in DC reactor | Yes |
| Built‑in EMC filter | No |
| Built‑in braking chopper | No |
| Built‑in PLC steps | 10000 steps(RTC real‑time clock) |
| Max pump quantity | 8 pumps |
| Dimension(W×H×D) | 420 mm × 800 mm × 300 mm |
| Weight | 105.0 kg |
| Cooling | Forced air cooling,replaceable modular fan |
| Enclosure rating | IP00 |
| Keypad | KPCC‑01,support remote extension |
| PCB Conformal coating | Class3C2 |
| Operation temp full rating | 0‑50℃ |
FAQ
1.VFD1600CP43A-00 – Overall width, height and depth dimensions of the machine, net weight of the machine, frame model?
The
- Frame model: F1 frame
- Overall dimensions of the machine (width 420 mm × height 800 mm × depth 300 mm)
- Net weight of the machine: 105.0 kg
2.How many water pumps can the VFD1600CP43A-00 single inverter directly control at most?
Supported. The Scheduled cycle mode (all variable frequency operation, no mains frequency bypass): The original system can accommodate up to 8 pumps, and only 1 pump operates in variable frequency mode at any given time.
3.Does the VFD1600CP43A-00 cooling fan support disassembly and replacement independently?
The Supports separate disassembly and replacement, does not support hot swapping. Equipped with speed detection, featuring pre-warning for fan lifespan.
4.For the VFD1600CP43A-00 model, how many pulses does the rectification have? Is a built-in DC reactor included?
The Rectification structure: 6-pulse rectification; DC reactor: Built-in standard configuration