Overview
The Delta CP2000 Series AC Drive, 460V, E1 frame, 6-pulse rectification, DC reactor, LD light-load 220A, ND heavy-load 180A, built-in PLC, hardware RTC (chronometer) with a 10-year lifespan, 8 pumps linked together, PCB circuit board fully covered with three-layer protection coating, IP00 open bare machine, wall-mounted screw installation, forced air cooling.
Specification
| Item | Specification |
|---|---|
| Model | VFD1100CP43A‑00 |
| Series | CP2000 Fan‑Pump Drive |
| Rated motor power | 110kW(150HP),3‑phase 380‑480V |
| Frame size | E1 |
| Output current ND/LD | 180A / 220A |
| Rectifier | 6‑pulse |
| Built‑in DC reactor | Yes |
| Built‑in EMC filter | No |
| Built‑in braking chopper | No |
| Built‑in PLC steps | 10000 steps(RTC real‑time clock) |
| Max pump quantity | 8 pumps |
| Dimension(W×H×D) | 370 mm × 733 mm × 282 mm |
| Weight | 64.7 kg |
| Cooling | Forced air cooling, replaceable fan |
| Enclosure rating | IP00 |
| Keypad | KPCC‑01, remote extension supported |
| PCB Conformal coating | Class3C2 |
| Operation temp | 0‑50℃ full rating |
FAQ
1.VFD1100CP43A-00 – Overall width, height and depth dimensions of the machine, net weight of the machine, frame model?
The
- Frame model: E frame (E1)
- Net weight of the entire machine: 63.6 kg
- Overall dimensions of the machine (width 370 mm × height 733 mm × depth 282 mm)
2.The reserved ventilation spacing between the upper and lower, as well as the left and right air ducts of VFD1100CP43A-00. What are the possible fault consequences caused by the blockage of the air ducts?
Supported. The
- Ventilation spacing reserved for ducts:
- Up and down direction: ≥ 150 mm
- Left and right direction: ≥ 50 mm
- Consequences of duct blockage failure: Trigger overheating pre-warning; Execute power reduction output; Report OH overheating fault; Variable frequency drive stops and trips protection;
3.How many total steps does the PLC program inside VFD1100CP43A-00 have?
The
- Built-in PLC program total steps: 10,000 steps (10K steps).
- Integrated hardware RTC perpetual calendar real-time clock, supporting sequential logic, timing start/stop, pump group timed rotation, etc. for automated control.
4.Does the VFD900CP43A-21 cooling fan support disassembly and replacement independently?
The At an altitude of 2500 meters, full power output is not possible. This altitude exceeds the maximum 2000 meters allowed by the standard for the grounding system specified in the manual. Both the insulation gap and heat dissipation are limited, so it cannot be directly used on the machine. An assessment and confirmation must be obtained before it can be implemented in the project.
Looking for Original New VFD1100CP43A-00 Delta CP2000 Series AC Drive 110kW 220A 125HP
We supply this VFD1100CP43A-00 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews