Product Introduce
6AV2124-0JC01-0AX0 is a SIMATIC HMI TP900 Comfort series touch human machine interface with 9-inch widescreen TFT display, 800 × 480 pixels, Front: IP65; Rear: IP20 Protection Rating, TIA Portal (WinCC Comfort) Configuration Software.
Parameter
| Parameter | 6AV2124-0JC01-0AX0 (TP900 Comfort) | 6AV2124-0GC01-0AX0 (TP700 Comfort) | 6AV2124-0MC01-0AX0 (TP1200 Comfort) | 6AV2124-0QC02-0AX1 (TP1500 Comfort) |
|---|---|---|---|---|
| Display Size | 9″ Widescreen | 7″ Widescreen | 12″ Widescreen | 15″ Widescreen |
| Resolution | 800 × 480 pixels | 800 × 480 pixels | 1280 × 800 pixels | 1280 × 800 pixels |
| Operation Mode | Multi-touch | Multi-touch | Multi-touch | Multi-touch |
| Communication Interfaces | 1×Profinet (2-port switch); Optional ProfiBus DP | 1×Profinet (2-port switch); Optional ProfiBus DP | 1×Profinet (2-port switch); Optional ProfiBus DP | 1×Profinet (2-port switch); Optional ProfiBus DP |
| Power Supply | 24 V DC (1.1 A typical) | 24 V DC (0.8 A typical) | 24 V DC (1.5 A typical) | 24 V DC (1.8 A typical) |
| Front Protection Rating | IP65 | IP65 | IP65 | IP65 |
| Rear Protection Rating | IP20 | IP20 | IP20 | IP20 |
| Configuration Software | TIA Portal (WinCC Comfort/Advanced) | TIA Portal (WinCC Comfort/Advanced) | TIA Portal (WinCC Comfort/Advanced) | TIA Portal (WinCC Comfort/Advanced) |
| Key Features | Recipe management, trend display, alarm logging | Basic process monitoring, compact size | High-resolution visualization, extended memory | Large-screen operation, multi-user access |
| Typical Applications | Machine tool operation, small production lines | Compact equipment, local control stations | Mid-sized production lines, process monitoring | Large-scale systems, central control rooms |
FAQ:
1.What are the maximum number of screens and variable points supported by 6AV2124-0JC01-0AX0?
Maximum number of screens: 1000 (configuration upper limit, actual number is affected by project memory usage)
Maximum number of variable points:
- External variables (variables that communicate with the PLC): 2048
- Internal variables (HMI local variables, such as recipes, intermediate variables): 8192
2.6AV2124-0JC01-0AX0 Can the Profibus DP communication module be expanded? What are the key points for hardware installation after expansion?
6AV2124-0JC01-0AX0 supports the expansion of the Profibus DP communication module. It needs to be equipped with the Siemens-specific 6AV2181-5AF00-0AX0 (CM PTP/DP communication module). After expansion, it can be connected to the Profibus DP bus network and communicate with the corresponding master/slave device.
Hardware installation points:
- Power-off operation: Disconnect the HMI external power supply before installation. It is strictly prohibited to plug or remove modules while power is on to avoid equipment damage.
- Mechanical fixing: Align the expansion module with the expansion slot on the back of the HMI, push it in along the guide rail and tighten the side fixing screws to ensure that the module and HMI fit tightly without looseness.
- Bus wiring: Use Profibus Class A shielded cable to connect the DP interface of the module and the bus network; the bus terminal equipment needs to turn the terminal resistor to ON, and the non-end equipment needs to turn to OFF.
- Address setting: Set the Profibus station address (range 1-125) through the DIP switch on the side of the module to ensure that there is no conflict with the addresses of other devices in the network.
- Configuration matching: Add the expansion module in the TIA Portal, and the configured baud rate and station address must be completely consistent with the actual hardware settings.
Looking for Original New SIMATIC HMI TP900 Comfort 6AV2124-0JC01-0AX0 9 Inch TFT Panel?