The Mitsubishi FX5UC-32MT/DS-TS ultra-thin compact PLC CPU main unit with 16 transistor outputs, spring clip without screws for terminal blocks, DC24V power supply, 8-channel high-speed counter, 4-axis independent pulse output, 35mm standard DIN rail, 48.1mm ultra-thin body, IP20 (for installation inside the cabinet)
Specification
| Item | Specification |
|---|---|
| Model Name | FX5UC-32MT/DS-TS |
| Series | MELSEC iQ-F FX5UC Ultra-compact CPU |
| Total Built-in I/O Points | 32 points (16 Input / 16 Transistor Output) |
| Output Type | MT: NPN Open Collector Transistor |
| Power Supply Type | DS: DC24V Power Supply, Sink/Source Universal Input |
| Terminal Type | TS: Spring Clamp Screwless Terminal Block |
| Operating Power Supply | DC 20.4 ~ 26.4V |
| Operating Current | 0.5A |
| Internal 5V Bus Output Current | 0.72A |
| Overall Power Consumption | 5W |
| Built-in Digital Input | 16 points (X0~X17) |
| Input Signal | DC24V, Sink/Source switchable |
| Input Current per Point | 4mA (DC24V) |
| Input Response Time X0~X5 | 2.5μs (High-speed dedicated) |
| Input Response Time X6~X17 | 30μs (Standard) |
| Digital Filter Range | 0 ~ 70ms adjustable |
| Isolation of Input Circuit | Photo-coupler isolation |
| Built-in Digital Output | 16 points (Y0~Y17), grouped 8 points per common terminal |
| Rated Load Voltage | DC 5 ~ 30V |
| Rated Current per Output (Resistive Load) | 0.3A |
| Rated Current per Output (Inductive Load) | 0.1A |
| Max Current per Common Terminal | 0.8A |
| Total Max Output Current (2 groups parallel) | 1.6A |
| Off-state Leakage Current | ≤0.1mA @ DC30V |
| Output Response OFF→ON | ≤10μs |
| Output Response ON→OFF | ≤50μs |
| Basic Instruction Execution Speed | 34ns per LD instruction |
| Program Memory Capacity | 64K steps (Flash ROM, data retention without battery) |
| Timer T | 1024 points |
| Counter C | 1024 points |
| Data Register D | 8000 points |
| File Register R | 32768 points |
| Tag Memory Capacity | 120KB |
| ROM Storage Space | 5MB |
| External Storage Support | SD/SDHC Card (Max 4GB) |
| Supported Programming Languages | LD, ST, FBD, SFC, Structured Multi-program |
| Built-in High-speed Counter Channels | 8 channels total |
| Max Frequency (X0~X5 dedicated channels) | 200kHz |
| Max Frequency (General multiplex channels) | 10kHz |
| Counting Modes | Single-phase single/double count, AB-phase 4x multiplication |
| Built-in Positioning Axis | 4 independent axes (Y0/Y1/Y2/Y3 pulse output) |
| Max Pulse Output Frequency | 200kHz |
| Pulse Output Formats | Pulse/Direction, Forward/Reverse Pulse |
| Positioning Functions | Zero return, multi-speed positioning, electronic cam, synchronous follow-up |
| Built-in Communication Interfaces | 1 × RJ45 Ethernet, 1 × RS485 Terminal Port |
| Ethernet Supported Protocols | MC Protocol, SLMP, Modbus TCP, CC-Link IE Field Basic |
| RS485 Supported Protocols | Modbus RTU, Mitsubishi 485 dedicated protocol, N:N Network |
| Max Local I/O Points (CPU + Extension Modules) | 256 points |
| Max Total Control Points (Including Remote I/O) | 512 points |
| Mounting Standard | 35mm DIN rail |
| Unit Width | 48.1mm ultra-thin body |
| Operating Ambient Temperature | 0 ~ 55°C |
| Storage Temperature | -20 ~ 75°C |
| Ambient Humidity | 5 ~ 95%RH (Non-condensing) |
| Vibration & Shock Resistance | Compliant with IEC 61131-2 |
| Protection Class | IP20 (Installed inside control cabinet) |
| Certifications | UL/cUL, CE (EMC & RoHS), KC, Marine Certifications (LR/NK/DNV/ABS/BV/KR) |
FAQ
1.Which two standard communication interfaces are included in the FX5UC-32MT/DS-TS?
The Equipped with two standard communication interfaces: RJ45 Ethernet interface and RS485 terminal communication interface.
2.What is the maximum I/O point count for the FX5UC-32MT/DS-TS host when combined with local expansion modules?
Supported. The The maximum local I/O points for the local expansion module are 256 points.
3.Does the FX5UC-32MT/DS-TS Ethernet interface support Modbus TCP communication?
The Support. The FX5UC-32MT/DS-TS body is equipped with an RJ45 Ethernet interface, natively compatible with Modbus TCP communication. Firmware version 1.60 and above can be directly configured as a Modbus TCP slave station within the GX Works3 parameters; lower version firmware can achieve master/slave Modbus TCP communication through Mitsubishi LQ protocol function blocks, and a single PLC can simultaneously connect up to 8 external Modbus TCP devices.
4.What is the maximum number of controllable points for the entire machine when the FX5UC-32MT/DS-TS includes remote I/O?
The When the FX5UC-32MT/DS-TS is combined with remote I/O modules such as CC-Link, AnyWire, and ASLINK, the total number of local I/O and remote I/O that the entire machine can control is 512 points.
Looking for Original New MELSEC iQ-F FX5UC-32MT/DS-TS PLC CPU Main Unit DC24V
We supply this FX5UC-32MT/DS-TS mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now !