Overview
The Delta CP2000 Series Drive 75kW 100HP 150A 460VAC three-phase, built-in reactor, built-in PLC, supports ladder diagram programming, multi-pump linkage, supports 8 pumps for alternate operation, intelligent PID regulator, backlit LCD panel, supports remote extension wiring installation on the panel, RJ45 port, cooling uses dual axial modular fans for forced air cooling, can be disassembled and replaced separately, PCB has three-layer anti-corrosion coating, D-frame, IP00, only the internal power circuit is protected by IP20,
Specification
| Item | Specification |
|---|---|
| Model | VFD750CP43B-00 |
| Series | Delta CP2000 Fan & Pump Inverter |
| Rated Motor Power | 75kW (100HP) |
| Input Spec | 3-phase 380~480VAC, 50/60Hz |
| ND Rated Current | 110A (Heavy Duty Constant Torque) |
| LD Rated Current | 150A (Light Duty Variable Torque) |
| ND Overload | 120%/60s, 160%/3s |
| LD Overload | 120%/60s |
| Max Output Frequency | 600Hz(V/F), 400Hz(SVC Sensorless Vector) |
| Control Mode | Multi V/F Curve, SVC Sensorless Vector |
| Built-in DC Reactor | Yes |
| Built-in EMC Filter | No |
| Built-in Brake Chopper | No |
| Cooling Mode | Forced air cooling, replaceable fan with life warning |
| PCB Protection | Full conformal anti-corrosion coating (3C2) |
| Built-in PLC Capacity | 10000 Steps |
| Multi-Pump Control | Max 8 pumps group linkage control |
| Native Communication | Modbus RTU, BACnet |
| Optional Bus Cards | Profibus-DP, CANopen, Modbus TCP, EtherNet/IP |
| Dimension(W×H×D) | 330mm × 550mm × 275mm |
| Net Weight | 37.2kg |
| Protection Grade | IP00 |
| Full-load Ambient Temp | ND:-10~50℃; LD:-10~40℃ |
| Non-derating Altitude | ≤1000m |
| Certifications | CE, UL, cUL |
FAQ
1.What are the overall length, width, depth and net weight of the VFD750CP43B-00 machine?
The
- Overall dimensions of the machine (width 330mm × height 550mm × depth 275mm)
- Net weight of the machine: 37.2kg
2.What are the standard ventilation spacing requirements for the upper and lower, as well as the left and right air ducts of the VFD750CP43B-00 inverter?
Supported. The
- Upward and downward air ducts (top and bottom)
- Minimum reserved space above the top outlet ≥ 100mm
- Minimum reserved space below the bottom inlet ≥ 50mm
- Left and right lateral spacing
- Minimum reserved space between the left and right side walls of the frequency converter and the cabinet, and other components on one side ≥ 30mm
- When two units of the same model are installed side by side horizontally, the distance between them ≥ 50mm
3.What is the total number of steps of the PLC program built into VFD750CP43B-00?
The 10,000 steps (10K Steps), equipped with a perpetual calendar real-time clock, capable of compiling control programs for timing control, logical interlock, pump group linkage, etc.
4.What is the anti-corrosion coating grade of the VFD750CP43B-00 PCB circuit board?
The Execution standard: IEC 60721-3-3 Class 3C2, one-component modified acrylic conformal three-proof coating, full board coverage spraying. The “3C2” indicates that it can stably withstand mild indoor corrosive gases, regular condensation, and dusty environments.
Looking for Original New Delta VFD750CP43B-00 CP2000 Series Drive 75kW 100HP 460VAC
We supply this VFD750CP43B-00 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now