Overview
The Delta VFD4A2MS43ANSAA MS300 Series Drive – Three-phase AC 380-480V – Normal light load: 1.5kW, Heavy load: 1.5kW, Built-in braking chopper, Panel as an optional external component, Built-in PLC, 2000-step program capacity, Built-in RS485 Modbus, USB debugging port, Forced cooling, Standard DIN rail snap-in installation, Also supports wall-mounted screws for cabinet installation, IP20
Specification
| Item | VFD4A2MS43ANSAA MS300 Drive |
|---|---|
| Series | Delta MS300 |
| Input | 3AC 380‑480V,50‑60Hz |
| Low overload ND | 1.5kW,4.6A |
| High overload HD | 1.5kW,4.2A |
| Output frequency | 0‑590Hz |
| Brake chopper | Integrated |
| EMC filter | Not integrated |
| Frame size | B1 |
| Dimension(H×W×D) | 142mm ×72mm ×143mm |
| Weight | 1.8kg |
| Ingress Protection | IP20 |
| Mounting | 35mm DIN‑rail / wall mount |
FAQ
1.VFD4A2MS43ANSAA frame model, overall height, width and thickness dimensions of the machine, and the net weight of the machine?
The
- Frame model: B1
- Overall dimensions of the machine (height 142mm × width 72mm × depth 143mm)
- Net weight of the machine: 1.8kg
2.How many DI, DO, AI and AO channels are onboard on the VFD4A2MS43ANSAA board?
Supported. The
- DI Digital Input: 5 multi-functional inputs (MI1-MI5), among which MI7 is a high-speed pulse input terminal
- DO Digital Output: 1 relay output, 1 collector-emitter open DFM multi-functional output
- AI Analog Input: 2 channels (AVI voltage input, ACI current input)
- AO Analog Output: 1 analog output
3.How many program steps are there in the built-in PLC of VFD4A2MS43ANSAA, and is the PID function also built-in?
The
- Built-in PLC program steps: 2000 steps
- PID Function: This device is equipped with a built-in PID function. No additional hardware options are required. It supports process closed-loop regulation and can be used for control of various conditions such as pressure, flow, and temperature.
4.The protection level of VFD4A2MS43ANSAA, which installation methods does it support? Does the DIN rail support it?
The
- Protection level: IP20 (Suitable for use inside the control cabinet only. Cannot be directly exposed to the outdoor environment.)
- Wall-mounted screws for the cabinet body are directly installed (built-in)
- 35mm standard DIN rail installation, requires an optional DIN rail installation adapter. The equipment body does not come with a rail clip and cannot be directly clamped onto the rail.
Looking for Original New Delta VFD4A2MS43ANSAA MS300 Series Drive 1.5kW B1
We supply this VFD4A2MS43ANSAA mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews