Overview
The Delta MS300 Series Drive Three-phase AC 380-480V, E1 frame, built-in braking chopper, pulse I/O, built-in PLC, PID closed-loop regulation function, RS485 Modbus, USB debugging port, forced air cooling, built-in detachable cooling fan, IP20, net weight: 4.7kg
Specification
| Item | VFD32AMS43ANSAA MS300 Drive |
|---|---|
| Series | Delta MS300 |
| Power supply | 3AC 380‑480V 50‑60Hz |
| ND Normal Duty | 15kW,36A |
| HD Heavy Duty | 15kW,32A |
| Output frequency | 0‑599Hz |
| Brake chopper | Integrated |
| EMC filter | Not integrated |
| Frame size | E1 |
| Dimension(H×W×D) | 250mm ×130mm ×185mm |
| Weight | 4.7kg approx |
| Ingress Protection | IP20 |
| Mounting | Wall mount /35mm DIN‑rail(need adapter) |
| Conformal Coating | 3C2 grade |
FAQ
1.Does VFD32AMS43ANSAA have a built-in braking chopper, and is the braking resistor internal or external?
The
- Built-in braking chopper: Yes.
- Braking resistor: External connection. The inverter body does not have a built-in braking resistor. An external matching power braking resistor needs to be selected and configured.
2.VFD32AMS43ANSAA frame model, overall height, width and thickness dimensions of the machine, and the net weight of the machine?
Supported. The
- Frame model: E1
- Overall dimensions of the machine (height 250mm × width 130mm × depth 185mm)
- Net weight of the machine: 4.7kg
3.How many DI, DO, AI and AO channels are onboard the VFD32AMS43ANSAA board?
The
- DI Digital Input: 5-channel multi-functional digital input, among which MI7 is a high-speed pulse input terminal (note: DI supports NPN/PNP jumper switch)
- DO Digital Output: 1 relay output, 1 DFM high-speed pulse open-collector output
- AI Analog Input: 2 channels
- AO Analog Output: 1 channel
4.How many program steps are there in the built-in PLC of VFD32AMS43ANSAA, and is the PID function included?
The
- Built-in PLC program steps: 2000 steps
- PID function: The device is equipped with built-in PID closed-loop regulation function. It supports 2 sets of PID, featuring positive and negative actions, sleep mode, and limit values. It can be used for closed-loop control of temperature, pressure, and flow.
Looking for Original New Delta VFD32AMS43ANSAA MS300 Series Drive 15kW 36A E1
We supply this VFD25AMS43ANSAA mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews
There are no reviews yet.