Overview
The ABB ACS880-01-038A-3 18.5 kW three-phase AC 380-415V built-in power side choke coil Pump, fan, extruder, crane, winch, ordinary conveyor No-sensor vector control RS-485 motor overheating protection Ground fault protection ACS-AP-W inverter
Specification
| Serial Number | Parameter Item | Detailed Technical Specification |
|---|---|---|
| 1 | Model | ACS880-01-038A-3 |
| 2 | Product Series | ABB ACS880-01 Wall-mounted Single Drive Inverter |
| 3 | Frame Size | R3 |
| 4 | Voltage Grade | 3-phase 380~415V AC |
| 5 | Installation Method | Wall-mounted / Cabinet installation |
| 6 | Protection Level | IP21 |
| 7 | Input Voltage Range | 323~456V AC (-15%~+10%) |
| 8 | Input Frequency | 47.5~63Hz |
| 9 | Light Duty Rated Power | 18.5 kW |
| 10 | Light Duty Continuous Current | 38 A |
| 11 | Heavy Duty Rated Power | 15 kW |
| 12 | Heavy Duty Continuous Current | 32 A |
| 13 | Short-time Maximum Output Current | 57 A (60s) |
| 14 | Output Frequency Range | 0~±598 Hz |
| 15 | Control Mode | DTC direct torque control, V/F control, Sensorless vector control |
| 16 | Applicable Motors | Asynchronous motor, Permanent magnet motor, SynRM motor |
| 17 | Built-in Standard Configuration | DC choke, EMC filter, Brake chopper |
| 18 | Digital Input | 6 channels, 24VDC |
| 19 | Digital Output | 3 groups of relay output |
| 20 | Analog Input | 2 channels (0~10V / 4~20mA optional) |
| 21 | Analog Output | 2 channels (0~10V / 4~20mA programmable) |
| 22 | Standard Communication | RS-485 Modbus RTU, USB debugging interface |
| 23 | Optional Fieldbus | PROFINET, EtherNet/IP, EtherCAT, PROFIBUS-DP, CANopen, DeviceNet |
| 24 | Safety Function | STO, SIL 2 / PL d |
| 25 | Overload Capacity | LD:110%/60s, HD:150%/60s |
| 26 | Full-load Efficiency | ≥98% |
| 27 | Operating Temperature | -15℃~+40℃ (No derating) |
| 28 | Altitude Adaptation | ≤1000m without derating |
| 29 | Cooling Mode | Air cooling with built-in fan |
| 30 | Net Weight | About 17~19kg |
FAQ
1.What type and how many channels does the standard digital output of ACS880-01-038A-3 have?
The
- Standard digital output: 3 channels
- Output type: Passive contact output via relay
2.What safety functions and overload capabilities does the ACS880-01-038A-3 inverter have?
Supported. The
-
-
- Standard equipped with STO safety torque cut-off, safety level: SIL2, PL d;
- Comprehensive electrical fault protection, motor overheating protection, equipment over-temperature protection.
2. Overload Capacity
- Light Load (LD): Operate at 110% rated current for 60 seconds, short-term 150% overload;
- Heavy Load (HD): Operate at 150% rated current for 60 seconds, instantaneous maximum 180% short-term overload.
-
3.Which types of motors can the ACS880-01-038A-3 inverter drive?
The At the
- Three-phase asynchronous induction motor
- Permanent magnet synchronous motor
- Synchronous reluctance motor
4.What configuration components are included in the standard configuration of the ACS880-01-038A-3 device?
The
- DC reactor (input choke coil)
- Built-in EMC electromagnetic compatibility filter
- Built-in braking chopper
- Equipped with cooling fan
- Standard control circuit, I/O basic module
Looking for Original New ACS880-01-038A-3 18.5 kW Three Phase AC 380-415V Frequency Converter
We supply this ACS880-01-038A-3 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now !


Reviews
There are no reviews yet.