Overview
The ABB ACS510-01-038A-4 18.5 kW Dedicated VFD for Fans and Pumps 38 A V/F Control (Quadratic Torque) / Sensorless Vector Control Built in Modbus RTU (RS485)
Specification
| Item | Specification |
|---|---|
| Model | ACS510-01-038A-4 |
| Rated Motor Power | 18.5 kW |
| Rated Output Current | 38 A |
| Input Voltage | 380~480 V 3-phase, ±10%, 48~63 Hz |
| Output Voltage | 0~Input Voltage |
| Output Frequency | 0~500 Hz |
| Protection Degree | IP21 (standard), IP54 (optional) |
| Control Mode | V/F control, Sensorless vector control |
| PID Function | Dual PID built-in |
| PFC Function | Supported, max.7 pumps |
| Standard Communication | RS485, Modbus RTU |
| Digital Inputs | 6 channels |
| Relay Outputs | 2 channels |
| Analog Inputs | 2 channels |
| Analog Outputs | 2 channels |
| Operating Temperature | -15°C ~ +50°C |
| Application | Fans, Pumps, Water supply, HVAC |
FAQ
1.What type of load is the ACS510-01-038A-4 variable frequency drive suitable for?
The Square-torque loads primarily consist of fans and pumps.
2.What is the standard communication protocol for the ACS510-01-038A-4?
Supported. The Communication Protocol: Modbus RTU
3.Does the How many pumps can the ACS510-01-038A-4PFC with PFC functionality control?
The
1 main pump + 6 auxiliary pumps
- One pump is driven by a frequency converter for variable frequency speed control.
- The six pumps are controlled by contactors controlled by the frequency converter.
4.How many analog inputs and outputs does the ACS510-01-038A-4 have?
The
- Analog Inputs: 2 Channels
- Analog Outputs: 2 Channels
Looking for Original New ACS510-01-038A-4 18.5 kW Dedicated Variable Frequency Drive 38 A
We supply this ACS510-01-038A-4 mainly to system integrators and maintenance teams for replacement and retrofit projects.