The Siemens SENTRON PAC3220 multi-functional power monitoring instrument, 400/690V AC, true RMS measurement, current transformer secondary 1A or 5A, capable of withstanding 10A continuously, 100A for a short time (1s), 100-250V AC/DC, allowing ±10% fluctuation, built-in Ethernet switch, 2 RJ45 ports, supports Modbus TCP, 2 digital inputs DI, 2 digital outputs DO, color graphic LCD screen, equipped with 4 local function keys, supports multiple languages, the instrument’s back is IP20. IP65 (sealed and installed on the panel of the cabinet)
Specificatio
| Item | Specification |
|---|---|
| Catalog No. | 7KM3220-0BA01-1DA0 |
| Series | SENTRON PAC3220 Multifunction Power Meter |
| Mounting | Panel mount, cutout 92×92mm, housing 96×96mm |
| Meas. Voltage | 400/690V AC, TRMS |
| Current Input | CT secondary 1A / 5A |
| Frequency | 45~65Hz |
| Auxiliary Supply | 100~250V AC/DC ±10% |
| Communication | 2 × RJ45 Ethernet, Modbus TCP, integrated switch |
| Onboard I/O | 2DI + 2DO pulse output |
| Accuracy Class | 0.5 for energy |
| Front Protection | IP65 |
| Operating Temp | -25℃ ~ +55℃ |
| Weight | Approx. 0.32 kg |
FAQ
1.What is the display type of 7KM3220-0BA01-1DA0? Does it have local operation buttons?
The Backlit graphic LCD display, equipped with 4 local function operation buttons, supporting menu switching, parameter viewing and local settings
2.What are the overall width, height, depth and net weight of the 7KM3220-0BA01-1DA0 complete machine?
Supported. The
- Dimensions (width 96 × height 96 × depth 56, units: mm)
- Net weight of the entire machine: 0.325 kg.
3.What is the number of Ethernet RJ45 ports for 7KM3220-0BA01-1DA0, and is it equipped with an internal switch?
The Equipped with 2 Ethernet RJ45 ports, the instrument has a built-in Layer 2 switch and supports the connection of devices via network cables in series.
4.What is the front protection level of panel 7KM3220-0BA01-1DA0, and what is the back protection level?
The When installed in a sealed manner, the front of the panel has a protection level of IP65, and the terminal area on the back of the instrument has a protection level of IP20.