2711P-RDK10C is a 10.4-inch color touch screen, 640×480 pixels, brightness 300cd/m², full-function keyboard (including F1-F16 function keys, numeric keys, navigation keys), 85-264V AC or 24V DC, maximum power consumption 70W, supports up to 512MB CompactFlash storage, supports RS-232 Serial port, Ethernet (10/100Mbps) industrial protocol.
Parameter
| Parameter | 2711P‑RDK10C | 2711P‑RDB10C | 2711PC‑T10C4D1 (Compact 1000) |
|---|---|---|---|
| Core Type | Keypad‑only display module (non‑touch) | Keypad + analog resistive touch display module | 10‑inch color touch terminal (integrated) |
| Display | 10.4‑inch TFT, 640×480, CCFL backlight (50,000h@25℃) | 10.4‑inch TFT, 640×480, CCFL backlight (50,000h@25℃) | 10‑inch LCD, 640×480, LED backlight |
| Input Method | Full‑function keypad (F1‑F16, numeric, navigation) | Keypad + analog resistive touch (1M actuations) | Touch screen, keypad optional |
| Power | 85‑264V AC / 18‑32V DC; Max 70W (DC) | 85‑264V AC / 18‑32V DC; Max 70W (DC) | 24V DC; Lower power consumption |
| Dimensions (W×H×D) | 399×248×55 mm, 2.9 kgRockwell Automation | 399×248×55 mm, 2.9 kg | 244×160×45 mm, 0.5 kg (compact) |
| Memory | 512MB RAM, 512MB non‑volatile (≈79MB user available) | 512MB RAM, 512MB non‑volatile (≈79MB user available) | 1GB DDR3 RAM, 8GB SSD |
| Communications | Ethernet, RS‑232, USB (basic) | Ethernet, RS‑232, USB (basic) | Ethernet (Auto‑MDI/MDI‑X), enhanced connectivity |
| Lifecycle Status | Discontinued (Sep 30, 2022)Rockwell Automation | Discontinued (Sep 30, 2022) | Active (compact alternative) |
| Key Use Case | Keypad‑centric industrial control (no touch need) | Mixed keypad + touch operation | Space‑saving integrated HMI terminals |
FAQ:
1.How to enable the remote monitoring function (VNC/FTP) supported by 2711P-RDK10C?
1. VNC activation (core steps)
Panel operation: Home→Settings→Control Panel→Server Config→VNC Server, check Enable + set a 7-8 digit password, restart the service
Client connection: Enter HMIIP:5900 (such as 192.168.1.100:5900) and enter the password (supports 2 concurrent connections)
2. FTP activation (core steps)
Panel operation: Home→Settings→Control Panel→Server Config→FTP Server, check to enable (optional to disable anonymous login and set account password)
Client connection: Fill in HMI IP for host, port 21, enter credentials (anonymous users use anonymous), default directory \Temp
2.What parameters need to be configured when 2711P-RDK10C communicates with ControlLogix PLC via Ethernet?
1. Basic network parameters (HMI+PLC same subnet)
IP / subnet mask: static configuration, same network segment (for example: HMI 192.168.1.100, PLC 192.168.1.101, mask 255.255.255.0)
Gateway: cross-subnet configuration, leave blank in the same network segment
Port: PLC fixed 44818 (EtherNet/IP)
2. HMI side configuration
Set a static IP on the panel: Home→Settings→Network Connection→Ethernet Adapter, restart to take effect
FactoryTalk View ME: Create a new connection, select the EtherNet/IP driver, fill in the PLC IP, Ethernet module slot number, and timeout (1000–3000ms)
Tag binding format: [shortcut] tag name
3. PLC side configuration
Studio 5000: Add the Ethernet module (1756‑ENBT/EN2T), configure the IP, and the slot is consistent with the physical
Enable EtherNet/IP and open TCP port 44818
4. Key parameters
Communication timeout: 1000–3000ms
Scan rate: 100–500ms
Connection type: explicit priority (tag reading and writing)
3.The 2711P‑RDK10C has been discontinued, what is its direct replacement? What is the hardware and software compatibility of alternative models?
| Item | 2711P‑RDK10C | Replacement Model 2711P‑B10C22D9P | Compatibility Notes |
|---|---|---|---|
| Form Factor | Display module (requires logic module e.g., 2711P‑RP8D) | All-in-one terminal (integrated display + logic) | Not plug-and-play; requires reinstallation |
| Display | 10.4-inch TFT, 640×480 | 10.4-inch TFT, 640×480 | Same dimensions; mounting cutout compatible |
| Communication | Ethernet, RS‑232, USB | 2× Ethernet, RS‑232, 2× USB | Protocol compatible (EtherNet/IP, etc.); more ports |
| Power Supply | 100–240V AC | 100–240V AC | Input compatible; reusable old power supply |
| Installation | Panel mount | Panel mount | Same cutout size; direct replacement for mounting position |