Overview
The AB SMC Flex Open-Type Solid-State Soft Starter 317A 125-125-250 Hp 460 VAC, Input voltage 200-480 V AC, Control voltage 100-240 V AC. Built-in 7 startup modes. Onboard IO 4 channels of DPI. Local operation panel with display. Built-in cooling fan. SCCR short-circuit rating. Supports line connection or delta-star. 6-wire motor control. Bottom plate screws for cabinet fixation.
Specificatio
| Item | Specifications |
|---|---|
| Model | 150-F317NBD |
| Series | SMC Flex Smart Motor Controller |
| Rated Current | 317 A |
| Motor Rating @460V AC | 125~250 Hp |
| Main Power | 3 Phase 200~480V AC,50/60Hz |
| Control Supply | 100~240V AC |
| Enclosure Type | Open, IP00 |
| Built-in Bypass Contactor | Yes |
| Programmable Aux Relay | 4 points |
| Operation Modes | 7 standard start/stop modes |
| PTC Input | Supported |
| Dimension | 445mm W × 300mm H × 260mm D |
| Weight | Approx 22 kg |
| Mounting | Panel mount, not DIN rail |
| Operating Temperature | 0 ~ 60℃ |
| Storage Temperature | -20 ~ 85℃ |
| Certifications | cULus, CE, CSA |
FAQ
1.Does the 150-F317NBD model have an internal SCR bypass contactor and what is its function?
The
- Built-in SCR bypass contactor.
- Function: After the motor completes startup and enters steady-state operation, the bypass contactor closes, short-circuiting the SCR thyristor. The main current flows through the contactor contacts, reducing the heat and power loss caused by the continuous conduction of the SCR, prolonging the service life of the thyristor, and simultaneously reducing the operating noise of the equipment.
2.How many programmable auxiliary relay contacts are onboard the 150-F317NBD board?
Supported. The Number of onboard programmable auxiliary relay contacts: 4 channels, each channel can be configured as normally open or normally closed.
3.What are the overall width, height, depth and net weight of the 150-F317NBD machine?
The
- Dimensions: Width 290mm × Height 600mm × Depth 276.5mm
- Net weight of the entire machine: Approximately 45.8kg
4.Which installation method does 150-F317NBD support? Can it be directly installed on DIN rails?
The
- Installation method: The cabinet back panel is fixed by screws and the panel.
- It cannot be directly installed on DIN rails. This equipment is heavy and belongs to an open-type high-power soft starter. There is no DIN rail fastening structure on the back.
Looking for Original New 150-F317NBD SMC Flex Smart Motor Controller 460V 317A
We supply this 150-F317NBD mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now