Overview
The Delta CP2000 Series Drive Three Phase 45kW 480VAC, ND 76A, LD94A, built-in DC reactor, no filter, supports multi-pump control, Modbus RTU, BACnet, PLC10000 step logic program, LCD liquid crystal operation panel, PCB three protection coating, D0-1 framework, does not support zero stacking close installation, IP00 (open type without enclosure protection)
Specification
| Item | Specification |
|---|---|
| Model | VFD450CP43S-00 |
| Series | Delta CP2000 Fan&Pump Drive |
| Rated Motor Power | 45kW |
| Input | 3-phase 380~480VAC, 50/60Hz |
| ND Rated Current | 73A (Heavy Duty) |
| LD Rated Current | 91A (Light Duty) |
| Overload ND | 120%/60s, 160%/3s |
| Overload LD | 120%/60s |
| Max Output Frequency | 600Hz(V/F), 400Hz(SVC) |
| Control Mode | V/F curve, Sensorless Vector(SVC) |
| Built-in DC Reactor | Yes |
| Built-in EMC Filter/Brake Chopper | No |
| Cooling | Forced air cooling, replaceable fan with life warning |
| PCB Protection | Full conformal coating |
| PLC Capacity | 10000 steps built-in PLC |
| Pump Control | Max 8 pumps group control |
| Native Communication | Modbus RTU, BACnet |
| Optional Bus | Profibus-DP, CANopen, Modbus TCP, EtherNet/IP |
| Dimension(W×H×D) | 256mm × 410mm × 275mm |
| Net Weight | 26.9kg |
| Protection Grade | IP00 |
| Full-load Temp | ND:-10~50℃; LD:-10~40℃ |
| Non-derating Altitude | ≤1000m |
| Certifications | CE, UL, cUL |
FAQ
1.What are the normal input voltage range and the upper/lower limit of fluctuations for VFD450CP43S-00, and what is the number of pulses in the rectification pulse structure?
The
- Input voltage parameters: Three-phase AC 380~480V, 50/60Hz;
- Allowed voltage fluctuation range: ±15%, the stable working limit range is 323V ~ 552V.
- Adopting a 6-pulse diode rectification architecture, the entire machine is equipped with an internal DC reactor as standard, which is used to suppress harmonics.
2.Does the VFD450CP43S-00 model have built-in DC reactor, EMC filter and braking chopper?
Supported. The Built-in DC reactor, without filter, without braking chopper
3.What are the overall length, width, height and net weight of the VFD450CP43S-00 machine, and what is the model of the frame?
The
- Frame model: D0-1 Frame (D0 Frame)
- Overall dimensions of the machine (width 256mm × height 410mm × depth 275mm)
- Net weight of the machine: 26.9kg
4.What is the number of PLC program steps built into the VFD450CP43S-00?
The
- Program capacity: 10,000 steps (10K Steps).
- In addition, eight local independent control functions can be realized.
Looking for Original New Delta VFD450CP43S-00 CP2000 Series Drive Three Phase 45kW
We supply this VFD450CP43S-00 mainly to system integrators and maintenance teams for replacement and retrofit projects.
Contact US to get a good prices now


Reviews